Back to feed
22Track

ICSA-26-225-08: Siemens Desigo DXR and PXC Controllers

Siemens Desigo · CVE-2026-59693
0 news outlets1 CERTs and agencies0 research labs

Assessment: Track

SSVC decision points: exploitation none, automatable no, technical impact partial, deployment high.

What is it?

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.

Evidence

Official warnings1National CERTs, government cyber security agencies and the vendor’s own advisories

Exploitation

  • Exploit code published (not verified by us)
  • Exploited in the wild (confirmed by a source)
  • Listed as known exploited (CISA KEV)
CVSS
4.3
EPSS
–
First seen
11 Aug 2026
Status
confirmed